34: End (P95)
35: Thermocouple Temp (SE) (P13) ! measure initial temp difference
1: 8 Reps
2: 1 2.5 mV Slow Range
3: 1 SE Channel
4: 1 Type T (Copper-Constantan)
5: 100 Ref Temp (Deg. C) Loc [ _________ ]
6: 41 Loc [ _________ ] ! loc 41..48 = initial temp difference
7: 1 Mult
8: 0 Offset
36: Timer (P26)
1: 0 Reset Timer
37: Do (P86)
1: 21 Set Flag 1 Low
38: Do (P86)
1: 12 Set Flag 2 High
39: End (P95)
40: If Flag/Port (P91) ! fire the heat pulse
1: 12 Do if Flag 2 is High
2: 30 Then Do
41: Set Port(s) (P20)
1: 0 C8..C5 = low/low/low/low
2: 11 C4..C1 = low/low/high/high
42: Beginning of Loop (P87)
1: 1 Delay
2: 0 Loop Count
43: Timer (P26)
1: 99 Loc [ _________ ]
44: If (X<=>F) (P89) ! fire heater for just 0.75 s
1: 99 X Loc [ _________ ]
2: 3 >=
3: .75 F ! change as required
4: 31 Exit Loop if True
45: End (P95)
46: Set Port(s) (P20)
1: 0 C8..C5 = low/low/low/low
2: 0 C4..C1 = low/low/low/low
47: Beginning of Loop (P87)
1: 1 Delay
2: 0 Loop Count
48: Timer (P26)
1: 99 Loc [ _________ ]
Page view 52