CS100 Barometric Pressure Sensor
4
4. Wiring
4.1 Datalogger Connection
Before connecting the barometer to the datalogger, a yellow warning label
must be removed from the pigtails (see Figure 2). The warning label
reminds the user of the importance of properly connecting the barometer to
the datalogger. Proper wiring is shown in Table 1.
Figure 2. CS100 as Removed from the Box
Table 1. Signal and Ground Connectors for CS100
Wire
CS106 Terminal
Datalogger
Single-Ended Measurement
Datalogger
Differential Measurement
Blue VOUT S.E. Input High Side of Diff Input
Yellow AGND
AG (CR10(X), CR500, CR510)
(Other Dataloggers)
Low Side of Diff. Input
Black GND
(21X, CR7, CR9000(X))
G (Other Dataloggers)
(21X, CR7, CR9000(X))
G (Other Dataloggers)
Green EXT TRIG
Control port (use to turn power
on/off)
Control port (use to turn power
on/off)
Red SUPPLY 12 VDC 12 VDC
Shield Shield G (CR10(X), CR500, CR510)
(Other Dataloggers)
G (CR10(X), CR500, CR510)
(Other Dataloggers)
Improper wiring may damage the CS100 beyond
repair.
WARNING
Yellow Warning Label